8、完成配置,下載至PROFIBUS主站,系統(tǒng)即可連同。
三、主站如何監(jiān)測UPS數(shù)據(jù)
見下表:PROFIBUS主站中的I/O地址與UPS內(nèi)部數(shù)據(jù)的對照表;主站依據(jù)這些地址可以監(jiān)測到UPS數(shù)據(jù)。
注意:PROFIBUS地址列出的是相對地址。
PROFIBUS與測量數(shù)據(jù)對照表
二進制區(qū)
| PROFIBUS address |
Bit meaning |
Meaning |
| IB0~IB3 |
Bit=0 |
Bit=1 |
| I0.0 |
Main 1 voltage |
normal |
Outside tolerance |
| I0.1 |
Chopper operation |
off |
on |
| I0.2 |
Batter circuit |
ok |
fault |
| I0.3 |
End of battery backup time |
no |
yes |
| I0.4 |
Charger status |
ok |
fault |
| I0.5 |
Check battery |
no |
yes |
| I0.6 |
Low batteryshutdown warning |
no |
yes |
| I0.7 |
Charger operating status |
off |
on |
| I1.0 |
Peak overload |
no |
yes |
| I1.1 |
Inverter overload |
no |
yes |
| I1.2 |
Inverter operating status |
off |
on |
| I1.3 |
Inverter thermal overload |
no |
yes |
| I1.4 |
K3N contactor status |
open |
closed |
| I1.5 |
Inverter connection status |
Not connected |
connected |
| I1.6 |
Mains 2 voltage |
normal |
Outside tolerances |
| I1.7 |
Mains 2 frequency |
normal |
Outside tolerances |
| I2.0 |
Mains 2 / inverter phase shift |
normal |
Outside tolerances |
| I2.1 |
Phase rotation |
ok |
fault |
| I2.2 |
Mains 2 overload |
no |
yes |
| I2.3 |
Mains 2 thermal overload |
no |
yes |
| I2.4 |
normal |
no |
yes |
| I2.5 |
danger |
no |
yes |
| I2.6 |
Downgraded |
no |
yes |
| I2.7 |
Low battery shutdown warning |
no |
yes |
| I3.0 |
End of backup time |
no |
yes |
| I3.1 |
Operating on battery power |
no |
yes |
電流區(qū)
| PROFIBUS address |
電 流 測 量 |
單 位 |
型 號 |
|
IW0 ===> IW8 |
S11 |
S31 |
S33 |
|
IW0 |
I1(I相1)逆變器 |
A |
yes |
yes |
yes |
|
IW1 |
I2(I相2)逆變器 |
A |
|
|
yes |
|
IW2 |
I3(I相3)逆變器 |
A |
|
|
yes |
|
IW3 |
I1(I相1)主2 |
A |
yes |
yes |
yes |
|
IW4 |
I2 (I相2)主2 |
A |
|
|
yes |
|
IW5 |
I3(I相3)主2 |
A |
|
|
yes |
|
IW6 |
I1(I相1)負載 |
A |
yes* |
yes* |
yes |
|
IW7 |
I2 (I相2)負載 |
A |
|
|
yes |
|
IW8 |
I3(I相3)負載 |
A |
|
|
yes |
電壓區(qū)
| PROFIBUS address |
電 壓 測 量 |
單 位 |
型 號 |
|
IW09 ===> IW16 |
S11 |
S31 |
S33 |
|
IW9 |
主1 電壓 |
V |
yes |
yes |
yes |
|
IW10 |
逆變器 V1 |
V |
yes |
yes |
yes |
|
IW11 |
逆變器 V2 |
V |
|
|
yes |
|
IW12 |
逆變器 V3 |
V |
|
|
yes |
|
IW13 |
主2 電壓 |
V |
|
|
yes |
|
IW14 |
負載 V1 |
V |
yes |
yes |
yes |
|
IW15 |
負載 V2 |
V |
yes |
yes |
yes |
|
IW16 |
負載 V3 |
V |
|
|
yes |
功率區(qū)
| PROFIBS address |
功率測量 |
單位 |
型號 |
| IW17 ===> IW19 |
S11 |
S31 |
S33 |
| IW17 |
視在功率 |
KVA |
yes* |
yes* |
yes* |
| IW18 |
負載 |
KVA |
yes* |
yes* |
yes* |
| IW19 |
負載比率 |
KVA |
yes* |
yes* |
yes* |
頻率和計數(shù)區(qū)
| 品 質(zhì) 測 量 |
型 號 |
| PROFIBS address |
頻率測量 |
單位 |
S11 |
S31 |
S33 |
| IW20 ===> IW22 |
| IW20 |
逆變器頻率 |
Hz |
yes |
yes |
yes |
| IW21 |
主2頻率 |
Hz |
yes |
yes |
yes |
| IW22 |
負載頻率 |
Hz |
yes |
yes |
yes |
| |
| IW23 ===> IW25 |
計數(shù)器 |
單位 |
S11 |
S31 |
S33 |
| IW23 |
測量計數(shù)器 |
|
yes |
yes |
yes |
| IW24 |
狀態(tài)計數(shù)器 |
|
yes |
yes |
yes |
| IW25 |
電池已使用次數(shù) |
|
yes |
yes |
yes |
電池區(qū)
| PROFIBS address |
品質(zhì)測量 |
單位 |
型號 |
| IW26 ===> IW28 |
S11 |
S31 |
S33 |
| IW26 |
電池電壓 |
V |
yes |
yes |
yes |
| IW27 |
電池后備時間 |
mn |
yes* |
yes* |
yes* |
| IW28 |
電池有效能量指示 |
KVA |
yes* |
yes* |
yes* |
(*):for Comet S11 or S31 5KVA models, this value is forced to zero when the load is powered by the emergency Mains.
|